Instruction Manual
HI 8001 & HI 8002
Panel-mounted and Wall-mounted
Fertigation Controllers
Manufacturers since 1978
These Instruments are in
Compliance with the CE Directives
Vista de página 0
1 2 3 4 5 6 ... 87 88

Resumo do Conteúdo

Página 1 - Fertigation Controllers

1Instruction ManualHI 8001 & HI 8002Panel-mounted and Wall-mountedFertigation ControllersManufacturers since 1978These Instruments are inComplianc

Página 2 - TABLE OF CONTENTS

103.3 FERTILIZATION CONTROLFertigation Controller can use up to 4 fertilizer tanks.Each irrigation program can specify the percentage for each type of

Página 3

11AGES). For each individual sector’s pH average see panel C 24 (SECTORAVERAGES). All pH averages can be deleted manually or at specified time ofday u

Página 5 - 2 GENERAL DESCRIPTION

13opening and closing of a valve through which a neutral solution is circulated.The amount of neutral solution added is relative to the opening of the

Página 6 - 3 FUNCTION DESCRIPTION

14can compensate for changes in the process variable (measurement) and is par-ticularly good for slowly moving processes. When a change occurs in the

Página 7

15- To erase all statistics, use panel S 61 (ERASE STATISTICS). Statistics indi-cates pH and conductivity averages for all irrigation programs and sec

Página 8

163.10 LOGGING FUNCTIONSThe Fertigation Controller has the capability to log the most important occurredevents and values of different parameters that

Página 9

174 USER INTERFACEThe Fertigation Controller’s user interface consists of a 4 x 20 character LCDand a 23-key keyboard.Keyboard structure.4.1 OPERATING

Página 10

18different controller entities (programs, sectors, fertilizers etc.) within the samepanel.- LEFT and RIGHT ARROWS KEYS can be used to move the cursor

Página 11

19- LEFT, RIGHT arrow keys allow navigation within the currently focuseddata object. If the cursor exceeds the boundaries of the data object then thef

Página 12

2Dear Customer,Thank you for choosing a Hanna Product. Please read this instructionmanual carefully before using the instrument.This manual will provi

Página 13

204.2 PANEL BROWSING METHODSIn consulting mode, two browsing methods are available to view each of the 62panels (screens) of the Fertigation Controlle

Página 14

2111 SOL RAD EXTENS 40 PH CONTROL12 MAN CORRECTION 41 COND CONTROL13 TOTAL CORRECTION 42 CORRECTIONS14 SECTOR STATE 43 SOLAR RAD IRRIG15 - 44 -16 FER

Página 15

225 PANEL DESCRIPTION5.1 GENERAL CONSULTINGThe following panels C 01 through C 29 are for the general consulting ofcontroller settings and current m

Página 16

23Although access to the controllers features are denied, the functionality of thecontroller is not directly effected if a password authentication seq

Página 17 - 4 USER INTERFACE

24NOTE:- If the user is logged in and the operational mode is CONSULTING MODE,this panel can be accessed anytime and from any panel using the HOME

Página 18

255.2.1 PROGRAM STATE – C 03PROG 08 ACTIVEStarted by Solar RadRepeat 02/05 13:15PROGRAM STATE C03The purpose of this panel is to allow the user

Página 19

26REMINDER: In CONSULTING MODE the ESC key can be used as a short-cut key to access this panel from any panel.5.2.2 PH STATE – C 04Prog 08 Ref=06.4

Página 20

27and is not program specific.S in = Real time value of EC input sensor. This is an option sensor input tomeasure the conductivity of the incoming wat

Página 21

28DayIndicates if the selected program is set to run on a daily schedule.PeriodIndicates if the selected program is set to run on a yearly schedule.Sy

Página 22 - 5 PANEL DESCRIPTION

29This panel displays the current irrigation state of the indexed program. Time orvolume can control irrigation and the above panel displays the set v

Página 23 - GENERAL INFO C01

35.4 Alarms Consulting ... 375.5 Log Consulting ...

Página 24 - SENSORS STATE C02

305.2.9 MAN CORRECTION – C 12Prog 08 +015% +00:05:55 13:15MAN CORRECTION C12This panel displays how much the programmed irrigation parameters

Página 25 - PROGRAM STATE C03

315.2.11 SECTOR STATE – C 14Prog 08 Sect 21/21Set 00:10:30+009:45Done 00:03:10 13:15SECTOR STATE C14This panel displays the state of each secto

Página 26

32This panel displays the set and current amount of fertilizer used for a specificprogram. The Fertigation Controller controls the dosing of 4 fertil

Página 27

33PauseThe set pause time value for the indexed agitator of the selected program.System clockNOTE: The agitator’s working time values can be specified

Página 28

345.3 STATISTICS CONSULTING5.3.1 TOTAL ACCUMUL – C 19From: 09-26 13:37;120007654L 13:15TOTAL ACCUMUL C19This panel provides a total

Página 29 - SOL RAD EXTENT C11

355.3.3 SECTOR ACCUMUL – C 21From: 09-26 13:37;12000:00:17 Sect 01/01 13:15SECTOR ACCUMUL C21This panel provides a total (in time or v

Página 30

365.3.5 PROGRAM AVERAGES – C 23From: 09-26 13:37;1205.3pH Prog 0106.7mS 13:15PROGRAM AVERAGES C23This panel provides a pH & EC avera

Página 31

375.4 ALARMS CONSULTING5.4.1 ACTIVE ALARMS – C 25Low level fert: 4ACTIVE Alarm26-12 14:36:22 13:15ALARM 02/07 C25This displays the active alarms

Página 32 - AGITATOR STATE C17

38pressed the Fertigation Controller will search for the logged data. If no data isfound the panel is shifted to C 28 (LOG) and “no records found” is

Página 33 - PROG LAST START C18

39SET key or via panel S 59 (SET LOG LEVELS). The UP and DOWN arrow keysare available to move between log records in a “select previous/next” manner.T

Página 34

41 THEORY OF FUNCTIONIrrigation is one of the most important operation in agriculture. With properirrigation the quality and quantity of crops can be

Página 35

405.7 PROGRAM SETTINGS5.7.1 ACTIVE TIMETABLE – S 31Between Prog 07Date: 01-04 31-10Time: 07:00 23:00ACTIVE TIMETABLE S31This panel allows the u

Página 36

41(for more details see Section 3.1 and Appendix 3):Work dayThe number of consecutive workdays.Program NumberReflects the selected program (can be sel

Página 37

425.7.4 START CONDITIONS – S 34Time cond y Prog 07Solar rad NExt tank: -- Link 02START CONDITION S34Using this panel we can set up how a particular p

Página 38

43allows the setting of the following parameters:Program NumberReflects the selected program (can be selected only inside panel C 03). SeeSection 5.2.

Página 39 - SET DATE & TIME S30

44mode, see panel S 53 (IRRIG CTRL MODE). The program number indexes thispanel (for more details see Section 3.1 and Appendix 3). This panel display

Página 40

455.7.9 SET FERTILIZERS – S 39 Prog 07Fer1=020% Fer2=055%Fer3=060% Fer4=040%SET FERTILIZERS S39The fertilizer dosing is controlled b

Página 41 - SET PRIORITY S33

46Alarm thresholdSelectable pH control alarm threshold represents the time interval (mea-sured in the Fertigation Controller’s control cycles) conside

Página 42 - Prog 07

47fertilization process. The program number indexes this panel. This panel displaysand allows the setting of the following parameters:ManualThe selec

Página 43

48program. If “Work” and “Pause” are set the agitator will function intermittentlyrelative to the time settings. In this panel the agitator number is

Página 44 - SET SECTORS S38

495.8 MANUAL COMMANDS5.8.1 MANUAL START – S 47Active program: 03Start program: -- ?PROG MAN START S47Each program can be manually started using thi

Página 45 - Prog 07

52 GENERAL DESCRIPTIONThe Fertigation Controller is a micro-processor-based system used in fertiliza-tion and irrigation control for greenhouses or op

Página 46

50Y (yes) can be entered next to the selected condition to change the controllerstate. Only the Y (yes) key will have effect in activating the appropr

Página 47

51Ctrl in Pre / PostPress Y (yes) then ENTER to control pH prior and after irrigation.Use acid in pHCtrlPress Y (yes) or N (no) then ENTER to control

Página 48 - FILTERS CTRL S46

525.9.4 CALIBRATE SENSORS – S 54 Channel: 01Now: 02.3 Ref: 02.5Status: First StageCALIBRATE SENSOR S54The sensor calibration procedure consist

Página 49 - STOP - WORK

53SensNr = The selectable number of pH sensors in the system (1 to 2).SensNr = The selectable number of EC sensors in the system (1 to 3).SDifThe maxi

Página 50 - Ctrl in Pre/Post Y

54ECkFactory amplification setting for EC control.ECTiIntegral constant for EC control. Setting the value to 99.9 minutes effec-tively disables the in

Página 51 - Volume control: N

55corded and can be inspected at the same time. Alarm events are stored regard-less of log level and can be inspected using panel C 27 (ANOMALY). Pa

Página 52 - Channel: 01

565.9.11 ERASE STATISTICS – S 61 Erase all: - On overflow: YDaily at hour: 00:01ERASE STATISTICS S61With this panel it is possible to erase stored

Página 53

576 CALIBRATION PROCEDURES6.1 SENSOR CALIBRATION PROCEDUREThe purpose of calibrating the Sensor’s used in conjunction with the FertigationController i

Página 54

586.2 PID TUNING PROCEDUREFor the PID controller, we have three working modes:1. With PID regulation algorithm (Proportional, Integrative and Derivati

Página 55 - SET PASSWORD S60

596.2.1 PID TUNING PROCEDUREDue to the fact that the pH and EC controls function with minimal error at thecontrol output value, the PID controller mus

Página 56 - Erase all:

63 FUNCTION DESCRIPTIONIn this chapter the main functions of the Fertigation Controller are presented. Fora better understanding see the typical insta

Página 57 - 6 CALIBRATION PROCEDURES

60A. NECESSARY STEPS FOR TUNING THE PID CONTROLLER FOR PH AD-JUSTMENT1. The pH of the water source used for irrigation is measured. When this value is

Página 58

6110. At the end of the program consult the log table. Write down in a table thevalues for the pH sensor and the time when the reading was done (see S

Página 59

62- Total number of sectors = 1- Irrigation time = 15 minute2. Go to panel S 38 (SET SECTORS) and check the above settings. If they aredifferent adjus

Página 60

63NOTE: The period of time for Irrigation time (15 minute default) - panel S 37(PRE/POST IRRIG) - can be modified (increased or decreased), if theproc

Página 61

64- The control function remains constant; however, a steady state offset ispresent meaning that the set point is never completely maintained.4. INTEG

Página 62

65sensor #1) is outside of the allowable dead band determined by the specified pHReference value together with the pH min and pH max offset limits. Th

Página 63

668 TROUBLE SHOOTING GUIDETHE CONTROLLER DOES NOT FUNCTIONCheck to insure that the proper voltage is applied to the controller. After con-necting the

Página 64 - 7 ALARM DESCRIPTION

67occurred that may not be correctable by the type and amount of acid (or base)being used. If the problem persists after checking the process pH and a

Página 65

689 ELECTRICAL DIAGRAMS

Página 67

7- The accumulated solar radiation starting level value is used as a thresholdvalue for the accumulated solar radiation. When the accumulated solarrad

Página 69

71POWERBOARDEXTENSIONBOARDMAINBOARD

Página 70

72APPENDIX 1- KEYBOARD OPERATING MODESCONSULTING MODE:- arrow keys can be used to navigate inside the currently focused object- ESC key can be used as

Página 71

73APPENDIX 2 - OUTLET ASSIGNMENT TABLEOUTLET NUMBER ASSIGNED ELEMENT08 Filter1 35 SECTOR VALVE 1209 Filter2 36 SECTOR VALVE 1310 pH 37 SECTOR VALVE 14

Página 72

74APPENDIX 3 - GRAPHICAL EXPLANATION

Página 75

77APPENDIX 4 - LIST OF PANELSGeneral InfoWORK Anomalies 00Prog 08 06.4pHSect 07 02.1mS 13:15GENERAL INFO C01Active Program: 0406.3pH 1200W/m2

Página 76

78Prog 08 Time Y Day Y Period Y 13:15WORK TIME COND C08Prog 08 Priority 05Conflict Programs 02 13:15PRIOR & CONFLICT

Página 77 - APPENDIX 4 - LIST OF PANELS

79Prog 02 Fert 02 Set 40%Current 20% 13:15FERTILIZ STATE C16Prog 08 Agitator 01Work 00:03 WORKPause 00:02 13:15AGITATOR STATE C1

Página 78

8SOLAR RADIATION FACTOR:- This option can be set using panel S 42 (CORRECTIONS). This factoraffects the irrigation time or volume extension in accorda

Página 79 - Program Settings

80Prog 07Repeats 04 Pause 00:30:00PROGRAM REPEATS S36 Prog 07 PreIrrig: 000:00:05PostIrrig: 000:00:05PRE/POST IRRIG S37Valve 05 Pr

Página 80 - Prog 07

81Pre 00:33 Prog 08Work 00:10Pause 00:05SET AGITATORS S45Link 05 Filter 01Clean on alarm: YClean time: 01:01:02FILTERS CTRL S46Controlle

Página 81 - Controller Settings

82Ctrl on pH alarm: YIrrig on pH alarm: Y Ctrl on EC alarm: YALARM BEHAVIOR S52Volume control: N Time control: YIRRIG CTRL MODE S53 Channel: 01N

Página 82 - Channel: 01

83Disable password: NNew password: ---SET PASSWORD S60Statistics ConsultingFrom: 09-26 13:37;120007654L 13:15TOTAL ACCUMUL C19Fro

Página 83 - Statistics Consulting

84Controller LoggingExt state:ACTIVEProg State changed.18-08 15:05:30 15:05Log 0012 Lev 03 C28Manual CommandsActive program: 03Start program: -- ?PRO

Página 84 - Manual Commands

85APPENDIX 5 - INSTALLATION BLOCK DIAGRAM

Página 86

87Recommendations for userBefore using this product, make sure that it is entirely suitable for the environment inwhich it is used.Operation of this i

Página 87 - WARRANTY

88www.hannainst.comMAN800107/03

Página 88

9sectors using one of the following ways:- Manually- Every day at specified hour- Automatically when the accumulations counter value overflows3.2 COND